Home > Circuit Breaker

  • DZ30LE Residual current circuit breaker
DZ30LE Residual current circuit breaker

DZ30LE Residual current circuit breaker


Instantaneous Trip Circuit Breaker Overload Protection Earth Leakage Circuit Breaker


Electrical
feature
Standard IEC/EN 61009-1
Type(wave form of the earth leakage sensed) AC
Thermo-magnetic release characteristic C
Rated current ln A 6,10,16,20,25,32
Poles P 1P+N
Rated voltage Ue V 230
Rated sensitivity I n A 0.03
Rated residual making and breaking capacity l m A 500
Rated short-circuit capacity Icn A 3000
Break time under I n s <0.1
Rated frequency Hz 50/60
Rated impulsewithstand voltage(1.2/50)Uimp V 4000
Dielectric test voltage at ind.Freq for 1min kV 2
Insulation voltage Ui V 250
Pollution degree 2
Mechanical
feature
Electrical life 4000
Mechanical life 10000
Fault current Indicator Yes
Protection degree IP20
Ambient temperature -5~+40(Special application please refer to
(with daily average 35 ) C temperature compensation correction)
Storage temperature C -25~+70
Installation Terminal connection type Cable/Pin-type busbar
Terminal size top/bottom for cable mm2 16
AWG 18--5
Terminal size top/bottom for busbar mm2 25
AWG 18--3
Mounting On DIN rail EN 60715(35mm)by means of fast clip device
Connection From top